Permit: T06CM04023

Parcel: 135061550

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/28/2007 BUILDING - FINAL Approved IVRS - Inspection :*
09/05/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RELOCATE CONDENSATE TO ABSORBENT SURFACE
08/24/2007 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) OPEN GROUND 2 RECEPTACLES EAST WALL MASTER
2) NO LOX ON ALUMINUM WIRES
3) BATH GFI'S DO NOT FUNCTION PROPERLY
4) OUTSIDE RECEPTACLES NOT GFI
5) SMOKIES NEED TO BE ARC FAULT
6) CONFIRM SIZE OF ALUMINUM WIRE TO #2 A/C
7) ROUTE A/C DRAIN TO PVC DRAIN
08/21/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED ALL FURNITURE, BOXES, AWAY FROM WALLS TO CONDUCT A PROPER INSPECTION
2) EXTERIOR RECEPTS NEED GFCI PROTECTION
3) PROVIDE ACCESS PANEL FOR JACUZZI TUB
4) SEDIMENT TRAP AT WATER HATER NEEDS TO BE ON APPLIANCE SIDE OF SHUT OFF VALVE
5) NOT A COMPLETE LIST
6) STOPPED INSPECTION