Permit: T06CM04015

Parcel: 116193770

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04015

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/13/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
PLEASE FAX LETTER TO ATTN: RAY MAJUTA
07/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OFFICE FURNISHINGS ARE REQUIRED TO BE IDENTIFIED AS SUITABLE FOR THEIR USE AS PER 2002 NATIONAL ELECTRICAL CODE AS PER THE FOLLOWING SECTIONS A 110.2; 110.3
2. PROVIDE INFORMATION ON INSTALLATION
3. FLEX LINE FROM TOP OF POWER POLES IN SOME INSTANCES NOT SUPPORTED JUST TIED INTO JUNCTION BOXES -- ONLY SUPPORT IS CLAMP TIE IN AT BOX, ALSO, SOME FLEX LINES JUST LAY ON T-BAR & TILES
4. VERIFY ONLY REQUIRED SUPPORT OR TIE INTO CEILING TILE IS BROWN PLASTIC COVER UNDER CEILING WHERE POLE GOES INTO CEILING.
05/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NOT READY FOR FINAL
OK FOR TEMP C OF O (FOR SET UP)

1. FIRST FLOOR EM LIGHTING & NL OK, NORMAL LIGHTING OK
2. PANEL SPAC - SCHEDULE ARRANGEMENT CHANGED PROVIDE AS BUILT CORRECTIONS, FOR FINAL
3. PNL SPHC - LB'S ON SSIDE CORRECT CONNECTION AF LB
4. PNL LDP OK
5. PNLS P1.2.3.4.5 OK
6. LOW VOLTAGE & COMM & DATA FOR FINAL CONNECTIONS
7. POWER POLES FOR FINAL
8. OUTSIDE POLE LIGHTS TO BE CHECKED ON FINAL
05/15/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
ALL WIRING TO BE COMPLETE FOR FINAL INSPECTION INCLUDING MOD. FURNITURE AND ALL LOW VOLTAGE CONTROL WIRING. CHECK PROPER WORKING CLEARANCES FOR PANELS.
04/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/04/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*