Permit: T06CM04015

Parcel: 116193770

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM04015

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
05/02/2007 ELECTRIC - INTERMEDIATE Partial Approval OK CEILINGS ROOMS #19, 21, 28
I WILL CHECK DEMO, RACEWAY SEAL ABOVE PANELS AND REMAINDER LOW VOLTAGE AT LATER DATE
05/01/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - AP canceled
04/27/2007 ELECTRIC - INTERMEDIATE Denied 1. LIGHT FIXTURES OK
2. QUESTIONNABLE REACH ON CONDENSATE PUMPS INSTALL ONE PLUGGED.
3. POWER POLES NOT IN - LEAVE TILES OUT FOR INSPECTION
4. OK OTHER THAN #2 , #3
5. FINISH DATA & COMMUNICATION CABLE FOR INSPECTION
6. FINISH ALL WIRING IN CEILING - IF ASSOCIATED WITH FIRE ALARMS OR LOW VOLTAGE OCCUPANCY SENSOR.
04/26/2007 ELECTRIC - INTERMEDIATE Partial Approval RMS 10, 11, 12, 22, 27 -- OK TO COVER
04/25/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - AP canceled
04/24/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - AP canceled
04/20/2007 ELECTRIC - INTERMEDIATE Partial Approval NOTES:
1. DATA/COMM LV CABLES NEED TO BE PLENUM RATED, INDIVIDUALLY SUPPORTED - SEE ART. 725 NEC
2. NEED TO INSP. TERMINATIONS INTO MODULAR FURNITURE FROM ABOVE CEILING ROOM #30
04/20/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - AP canceled
ROOM 30 CEILING TILES
04/18/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - AP canceled
04/17/2007 ELECTRIC - INTERMEDIATE Partial Approval 1. OK WATER & BUILDING STEEL BONDING
2. BE ADVISED THAT DATA/COMM. CABLING WILL NEED TO BE PLENUM RATED & INDIVIDUALLY SUPPORTED IN A WORKMANSHIP LIKE MANNER PER 725 NEC
04/16/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - AP canceled
04/04/2007 ELECTRIC - INTERMEDIATE Partial Approval VFD'S NEED 36" IN FRONT WORKING CLEARANCE
04/03/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - AP canceled
03/26/2007 ELECTRIC - INTERMEDIATE Partial Approval OK 4" FEED BETWEEN MAIN 400A AT DSA TO PANEL SPHL OK TO TIE IN
03/23/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1. TWO FIRST FLOOR BATHROOMS - CEILING OK
2. PANEL SPHC OK
3. TRANS T-3 OK TIGHTEN GROUND LUGS UNDER T-3 NUTS/LN'S
4. TIGHTEN 90 DEG. 4" FLEX ON FLEX SIDE
5. TRANS T-3 OK - ADD WATER BOND WHEN AVAILABLE
6. PNL LDP OK
7. PNL SPLC, SPLD, SPCE
8. WILL NEED TO SEE TERMINATIONS AT MAIN GEAR FOR POWER RELEASE
03/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ENTRY AREA OK
03/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RMS 17, 18, 19, 21, 1, 2, 3, 4, 5, 6, 7, 8, 13, 14
OK TO COVER
02/22/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER BATHROOMS, AND ROOM #8, 9 WALLS
02/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ROOMS #10, 11, 12
02/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ROOMS #011, 010, 030, 025, 019, 029 AND 018 WALLS OK
2) ALSO #2 GEC FOR TRANS ON MEZZ TO OUTSIDE 2 GROUND RODS AND GROUND RING (EXISTING)