Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM04008
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL AIR BALANCE OK |
|
02/22/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* HP10 DISCONNECT NOT FUSED CORRECTLY. SECURE LOW VOLTAGE CONDUIT. HP9 OVERFUSED MARK THE DATA PLATE FOR HP1 UNITS NOT INTERLOCKED WITH EXHAUST FANS HP 3 & 6 NEED AIR BALANCE REPORT |