Permit: T06CM04008

Parcel: 13013059A


Addresses:

3801 E 34TH ST #105

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
02/22/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
02/07/2007 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLANS DO NOT INDICATE USE OF INADEQUATE DUCT INSULATION PER ASHRAE 90.1. REVISE PLANS TO PROVIDE A LETTER FROM THE OWNER ACCEPTING THE INADEQUATE DUCT INSULATION
02/05/2007 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DUCTS NOT INSULATED PER PLANS OR PER CODE
2) R4 WAS USED-R5 IS REQUIRED