Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 02/07/2007 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLANS DO NOT INDICATE USE OF INADEQUATE DUCT INSULATION PER ASHRAE 90.1. REVISE PLANS TO PROVIDE A LETTER FROM THE OWNER ACCEPTING THE INADEQUATE DUCT INSULATION |
|
| 02/05/2007 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DUCTS NOT INSULATED PER PLANS OR PER CODE 2) R4 WAS USED-R5 IS REQUIRED |