Permit: T06CM04003

Parcel: 124041020

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM04003

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/02/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1. SUPPORT GAS PIPING PER TABLE 3-1 2003 UPC
2. SEAL EXTERIOR WALL PENETRATION
3. PROVIDE SEDIMENT TRAP AT ROOFTOP UNIT
FLEX CONNECTOR MISSING RATING RING
4. REVISED PLAN ALLOWS ARMAFLEX
5. SUPPORT MIXING VALVE AT LAVATORY
INSULATE HOT WATER PIPING AT LAVATORY
6. ALL INDIRECT WASTE PIPING TO BE APPROVED MATERIAL, GRAVITY DRAIN (PLACE DISCHARGE VALVE AT SINK)
7. I.W PIPING TO BE INSTALLED TO PREVENT SPLASHING
8. 3-COMP SINK NOT INSTALLED PER PLAN
NOR INSTALLED PER CODE.
MISSING IS FLOW CONTROL AND VENT
02/07/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SEE NOTE FROM 11/14/06-HAVE GAS ADDED 03050 TO PERMIT AND HAVE GAS ADDED TO PLAN AND CALL THIS INSPECTION IN THRU THE IVR
2) INSULATION NOT PER PLAN-OK TO COVER WALLS SUBJECT TO PLAN REVISION
01/31/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO INSULATE HOT WATER PIPING PER PLAN
2. SUPPORT VERTICAL PIPE
SUPPORT HORIZONTAL PIPE
3. ABS "SHIMS" NOT PERMITTED
4. TEST ALL PIPE THRU THE ROOF
COPPER NOT COMPLETE
DO NOT COVER!