Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM04003
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1. SUPPORT GAS PIPING PER TABLE 3-1 2003 UPC 2. SEAL EXTERIOR WALL PENETRATION 3. PROVIDE SEDIMENT TRAP AT ROOFTOP UNIT FLEX CONNECTOR MISSING RATING RING 4. REVISED PLAN ALLOWS ARMAFLEX 5. SUPPORT MIXING VALVE AT LAVATORY INSULATE HOT WATER PIPING AT LAVATORY 6. ALL INDIRECT WASTE PIPING TO BE APPROVED MATERIAL, GRAVITY DRAIN (PLACE DISCHARGE VALVE AT SINK) 7. I.W PIPING TO BE INSTALLED TO PREVENT SPLASHING 8. 3-COMP SINK NOT INSTALLED PER PLAN NOR INSTALLED PER CODE. MISSING IS FLOW CONTROL AND VENT |
|
02/07/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SEE NOTE FROM 11/14/06-HAVE GAS ADDED 03050 TO PERMIT AND HAVE GAS ADDED TO PLAN AND CALL THIS INSPECTION IN THRU THE IVR 2) INSULATION NOT PER PLAN-OK TO COVER WALLS SUBJECT TO PLAN REVISION |
|