Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04003
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED NEC 408.4 2. PROVIDE DISCONNECTING MEANS FOR WATER HEATER NEC 422.31 B 3. 4 11/16 BOX @ POS NOT GROUNDED - NEC 250.148 GROUND ALL METAL BOXES 4. POS RECEPTACLE BOX OVERFILLED - NEC 314.16 5. HAVE SEVERAL LOOSE RECEPTACLES - NEC 406.4 6. AC DISCONNECT BONDING SCREW IS LOOSE 7. PROVIDE GFI PROTECTION FOR ALL KITCHEN AREA RECEPTACLES OR SINGLE 20 AMP RECEPTACLE IF FOR A SPECIFIC APPLIANCE - NEC 210.8 |
|
03/21/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. VERIFY 310.15 2. CLEAN EXCESS DIRT FROM PANEL 3. CHECK SERVICE NEXT INSPECTION 4. A BOND WILL NEED TO BE POSTED FOR TEMP POWER FOR TEST |