Permit: T06CM04003

Parcel: 124041020

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED
NEC 408.4
2. PROVIDE DISCONNECTING MEANS FOR WATER HEATER
NEC 422.31 B
3. 4 11/16 BOX @ POS NOT GROUNDED - NEC 250.148 GROUND ALL METAL BOXES
4. POS RECEPTACLE BOX OVERFILLED - NEC 314.16
5. HAVE SEVERAL LOOSE RECEPTACLES - NEC 406.4
6. AC DISCONNECT BONDING SCREW IS LOOSE
7. PROVIDE GFI PROTECTION FOR ALL KITCHEN AREA RECEPTACLES OR SINGLE 20 AMP RECEPTACLE IF FOR A SPECIFIC APPLIANCE - NEC 210.8
03/21/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. VERIFY 310.15
2. CLEAN EXCESS DIRT FROM PANEL
3. CHECK SERVICE NEXT INSPECTION
4. A BOND WILL NEED TO BE POSTED FOR TEMP POWER FOR TEST