Permit: T06CM04001

Parcel: 107092230


Addresses:

455 W KELSO ST #138


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM04001

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/22/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/15/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COVER PNL GUTS SO THEY WILL NOT BE SPRAYED.
2. ONLY NEW WORK - ADD SMOKE DETECTOR TO HALL - OK
3. SUPPORT BATHROOM LIGHT CORRECTLY.
4. ROMEX ENTERING 3-GANG BOX FOR SWITCHING NOT IN BOX CORRECTLY ALSO USE METAL PLATE TO PROTECT WIRING AT STUD BEHIND SWITCH.
5. NAIL RANGE FEEDER TO STUD IN KITCHEN.