Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* WORK IN PROGRESS |
|
| 04/10/2007 | ELECTRIC - FINAL | Denied | 1. ON ROOF - NEED PROPER FUSE SIZES, PROPERLY IDENTIFY EQUIPMENT. 2. PROVIDE PROPER FRONT CLEARANCE FOR WH DISCONNECT 3. CHECK EMERGENCY LIGHTING FOR PROPER OPERATION 4. SWAMP COOLERS NOT WORKING 5. PROPERLY DERATE CONDUCTORS IN RACEWAYS, GUTTERS 6. FINISH MISC. WIRING OK TO OCCUPY FOR THE PURPOSE OF SET UP ONLY |