Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 03/30/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. INSTALL ADDRESS ON SERVICE 2. IDENTIFY SERVICE DISCONNECTS - NEC 230.70 B & PANELS 3. TIGHTEN ALL CONNECTIONS -- NEC 110 4. PULL & MAKE UP SECONDARYS 5. BOND SERVICE RISERS -- NEC 250.90, 250.102 6. TIGHTEN ALL FITTINGS, LOCKNUTS - NEC 110 7. BOND RACEWAYS TO GUTTER - NEC 250.90, 250.102 8. BOND NEUTRALS TO SERVICE DISCONNECT ENCLOSURES NEC 250.24B 9. TERMINATE FEEDER EQUIPMENT GROUNDS TO NEUTRAL BARS NOT TO ENCLOSURE - NEC 110.3 10. BONDING CONDUCTOR FOR WATER TO BE BONDED TO SERVICE NEUTRAL - NEC 250.102 11. BONDING CONDUCTOR FOR RACEWAYS GUTTER TO DISCONNECTS UNDERSIZED - NEC 250 12. BOND SPRINKLER PIPE - NEC 250.104 13. BOND GUTTER - NEC 250.90, 250.102 CHECK GUTTER - NEC 366.6 |