Permit: T06CM03998

Parcel: 10309044B


Addresses:

4055 N RUNWAY DR

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
04/02/2007 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
03/30/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
The service is not per code.| 210*
1. INSTALL ADDRESS ON SERVICE
2. IDENTIFY SERVICE DISCONNECTS - NEC 230.70 B & PANELS
3. TIGHTEN ALL CONNECTIONS -- NEC 110
4. PULL & MAKE UP SECONDARYS
5. BOND SERVICE RISERS -- NEC 250.90, 250.102
6. TIGHTEN ALL FITTINGS, LOCKNUTS - NEC 110
7. BOND RACEWAYS TO GUTTER - NEC 250.90, 250.102
8. BOND NEUTRALS TO SERVICE DISCONNECT ENCLOSURES
NEC 250.24B
9. TERMINATE FEEDER EQUIPMENT GROUNDS TO NEUTRAL BARS NOT TO ENCLOSURE - NEC 110.3
10. BONDING CONDUCTOR FOR WATER TO BE BONDED TO SERVICE NEUTRAL - NEC 250.102
11. BONDING CONDUCTOR FOR RACEWAYS GUTTER TO DISCONNECTS UNDERSIZED - NEC 250
12. BOND SPRINKLER PIPE - NEC 250.104
13. BOND GUTTER - NEC 250.90, 250.102

CHECK GUTTER - NEC 366.6