Permit: T06CM03998

Parcel: 10309044B


Addresses:

4055 N RUNWAY DR

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
04/13/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/19/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILE INSTALLATION
DATA, L.V WIRING NOT IN
WILL LOOK BEFORE CEILING ON FINAL
03/15/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CHECK ALL BOX FILL -- NEC 314.16
2. USE WIRE NUTS AS LISTED - NEC 110.3B
3. SECURE HANGING RACEWAYS @ BOTH ENDS - NEC 300.11
4. FINISH ALL WIRING - INCLUDE LOW VOLTAGE - ALL LOW VOLTAGE TO BE RAN IN A NEAT AND WORKMAN LIKE MANNER NOT USING GRID SUPPORT WIRES, ETC.