Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 03/19/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILE INSTALLATION DATA, L.V WIRING NOT IN WILL LOOK BEFORE CEILING ON FINAL |
|
| 03/15/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CHECK ALL BOX FILL -- NEC 314.16 2. USE WIRE NUTS AS LISTED - NEC 110.3B 3. SECURE HANGING RACEWAYS @ BOTH ENDS - NEC 300.11 4. FINISH ALL WIRING - INCLUDE LOW VOLTAGE - ALL LOW VOLTAGE TO BE RAN IN A NEAT AND WORKMAN LIKE MANNER NOT USING GRID SUPPORT WIRES, ETC. |