Permit: T06CM03987

Parcel: 10612017R

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/15/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/28/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER WALLS
SECURE STUB OUTS AT HAND SINK
SUPPORT OVERHEAD COPPER
CALL FOR INSPECTION FOR CLOSET FLANGES BEFORE SETTING TOILETS.
07/20/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ABS DWV UNDERSLAB OK TO COVER.
07/19/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
TWO WAY CLEANOUT FITTING IS NOT LISTED
TO BE INSTALLED IN THE VERTICAL POSITION,
NOR AS A TEST FITTING.
07/18/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. THE PLAN WAS DRAWN AND APPROVED IN ERROR.
MAY NOT DISCHARGE A DRAIN INTO A VENT (LAVATORIES).
2. FEMALE ABS THREADED FITTINGS NOT PERMITTED IN INACCESSIBLE LOCATION.