4975 N 1ST AV

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
10/18/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
10/12/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ALL AREAS
09/30/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO CALL IN AND HAVE APPROVED ALL REQUIRED INSPECTION: INCLUDING 03055 SEWER/HCS - 03050 GAS PRESSURE TEST
2. 3" TYPE K SILFOS'D JOINTS FROM METER LOCATION
TO TIE IN
3. CLOSET FLANGES OK
08/31/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- SEWER HAS NOT BEEN APPROVED
- NO WATER TO BLDG
- GAS HAS NOT BEEN APPROVED
- CONTRACTOR REQUESTS TEMP C OF O FOR TEN UNITS SUBJECT TO BLDG. OFFICIAL
- PROVIDE FOLLOW UP ON ALL PREVIOUS CORRECTIONS
08/23/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/17/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
2" GALV AND PLASTIC ELEVATOR SUMP DISCHARGE UP AND OVERHEAD AND DOWN TO BUILDING EXTERIOR. NEED TO SEE CONNECTIONS TO TANK AND REVISED DETAIL
07/17/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/16/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. AREAS DRAINS, FIRST AND SECOND FLOOR, AT DINING AND ACTIVITY ROOMS OK TO COVER
WATER TEST OK
2. PVC DWV 1ST FLOOR COMPLETE -- OK TO COVER
3. OVERHEAD COPPER 1ST FLOOR OK
07/06/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. FIRST FLOOR 2ND QUAD PVC DWV WATER TEST OK
SECOND FLOOR, PVC DWV OK TO COVER
2. WILL CHECK MID-STORY GUIDES WHEN I INSPECT WATER
3. NEED TO SEE CLOSET FLANGES
06/26/2007 PLUMBING - INTERMEDIATE Partial Approval 1. THIRD FLOOR COMPLETE:
DWV COPPER OK TO COVER THIS FLOOR
2. SECOND FLOOR SECOND QUAD PVC DWV OK
06/12/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. GAS PRESSURE TEST OK
2. WALKED 2ND FLOOR
3. OVERHEAD COPPER 3RD FLOOR OK TO INSULATE
05/23/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ROOF DRAIN EAST QUAD (QUAD #ONE) OK TO COVER
2. WELD GAS PIPE THIRD QUAD TESTED AT 60#
05/21/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
EAST QUAD -- ALL THREE FLOORS OK TO COVER AS INSULATOR COMPLETES HIS WORK
CLOSET FLANGES OK
WATER TEST OK
PRESSURE TEST OK
05/18/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/19/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SEE INSTALLATION STANDARD NUMBER 9
NO FEMALE THREADS IN INACCESSIBLE LOCATION
2. OVERHEAD COPPER OK
HOT INSULATED OK