Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* AFTER CORRECTIONS 1. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 2. LABEL UNITS OR DISCONNECTS |
|
| 01/16/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PREVIOUS CORRECTIONS ARE IN PROGRESS *NOTE: I WILL BE AWAY FROM THE OFFICE STARTING 1/19/08 AND RETURNING 2/4/08 FINAL ELECTRICAL APPROVAL WILL ONLY BE GIVEN BY ME AND WILL NEED TO WAIT FOR MY RETURN ON 2/4/08 IF CORRECTIONS ARE NOT COMPLETED BY 1/18/08 |
|
| 01/15/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/14/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/10/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PARTIAL INSPECTION ONLY INSPECTION FOR OPERATION OF EMERGENCY GENERATOR AND ASSOCIATED EQUIPMENT 1. REVISED PLANS FOR GENERATOR SHOWS A REDUCTION IN LOADS FOR PANELS "DBE" AND "LS" BUT DOES NOT STATE WHAT LOADS HAVE BEEN ELIMINATED - PROVIDE CLARIFICATION 2. NEW EQUIPMENT INSTALLED AFTER INITIAL FINAL INSPECTION TO BE REVISED/INSPECTED PARTIAL INSPECTION 3. COMPLETE ALL PRIOR CORRECTIONS |
|
| 01/09/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED CONTRACTOR ON SITE |
|
| 11/16/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PLANS TO BE REVISED AND APPROVE BEFORE FURTHER INSPECTIONS TAKE PLACE. |
|
| 11/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) GENERATOR AND 1 LINE DIAGRAM TO BE REVISED |
|
| 11/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION FOR SITE/EXTERIOR ELECTRICAL 1. PROVIDE SERVICE RECEPTACLE FOR HVAC EQUIPMENT 2. RACEWAY TO IRRIGATION CONTROL TO BE MINIMUM 18" BELOW GRADE - EMT NOT TO BE UNDER GRADE 3. FINISH ALL EXTERIOR WIRING AND FIXTURE INSTALLATION 4. POLE BASES TO BE GROUNDED WITH MIN. #10 CU GROUND, INSTALL MISSING J-BOXES COVERS 5. TEMPORARY SERVICE TO BE DE-ENERGIZED AND REMOVED AND ASSOCIATED EQUIPMENT 6. IDENTIFY DISCONNECTS (WALK IN'S CONDENSING UNIT) 7. WIRE NUTS USED BELOW GRADE TO BE LISTED FOR WET LOCATIONS MISC. 1. SEAL INTERIOR OF RACEWAYS INTO WALK IN'S 2. ALL PANEL DIRECTORY'S TO BE CORRECTLY IDENTIFIED 3. ONE LINE/GENERATOR PLAN TO BE REVISED & RE-APPROVED INSTALLATION NOT PER PLAN @ THIS TIME. |
|
| 11/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR GENERATOR/EMERGENCY SYSTEM ONLY PARTIAL INSPECTION 1. PLAN SHOWS 600 AMP BREAKER AT GENERATOR FOR ATS "F" FEEDER 2. PLANS SHOW LOAD BANK FOR GENERATOR 3. PLANS DO NOT SHOW FEEDER SIZE FOR GENERATOR TO ATS "E" 4. GENERATOR SIZE IS UNDER CALCULATED LOAD FOR GENERATOR - NEC 700.5A 5. IDENTIFY ALL EMERGENCY EQUIPMENT AS COMPONENTS OF EMERGENCY SYSTEM - NEC 700.9 NOTE: HAVE SEVERAL FEEDERS/OVERCURRENT NOT PER PLAN? SINGLE LINE DIAGRAM TO BE REVISED OR INSTALL PER PLAN |
|
| 11/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/05/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PARTIAL INSPECTION - OK CEILING TILES IN KITCHEN, LAUNDRY AND TELCOM ROOMS. NOTE: REMOVE BOXES SO THEY DO NOT COVER WALK IN FAN COIL DATA PLATES |
|
| 11/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR MAIN LEVEL KITCHEN ROOM #147 1. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND PROPERLY SUPPORTED @ 6' INTERVALS, SLACK WIRES USED TO SUPPORT EQUIPMENT IS TO BE SECURED @ BOTH ENDS 2. ALL 120V 15/20 AMP RECEPTACLES IN KITCHEN AREA TO BE GFI PROTECTED 3. DISCONNECT FOR DISPOSAL NEEDS PROPER FRONT WORKING CLEARANCE 36" 4. STRAP SEAL TIGHT WITHIN 12" OF TERMINATIONS 5. PANEL DIRECTORY TO BE CORRECTLY IDENTIFIED 6. SWITCH FOR DISHWASHER HOOD TO BE WEATHERPROOF 7. PROVIDE INSTALL MANUAL FOR ANSUL OTTOMAN BOX 8. BOXES CONTAINING FIRE ALARM TERMINATIONS TO BE RED PARTIAL INSPECTION FOR THIS AREA |
|
| 10/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY - AFTER HOURS INSPECTION CHK #30313 FOR $450.00 RECEIVED INSPECTION FOR THE INTERIOR OF FIRST AND SECOND FLOORS ONLY - 1. FINISH ALL WIRING 2. LIGHT FIXTURES, DIMMERS, EQUIPMENT TO BE PROPERLY GROUNDED 3. BOX EXTENDERS NEEDED WHERE BOX SIT BACK MORE THAN 1/4" OR LESS THAN FLUSH TO COMBUSTIBLE SURFACE 4. OVERRIDE SWITCH FOR BATH LIGHTS NOT WORKING 5. IDENTIFY WHITE CONDUCTORS USED AS HOT 6. PROPERLY IDENTIFY ALL PANEL DIRECTORIES 7. PROPERLY SIZE EQUIPMENT GROUNDS TO CONTACTOR J-BOXES 8. INSTALL ALL GFI BREAKERS PER PLAN 9. PROPERLY INSTALL DRYER TAILS, REMOVE BOND JUMPER 10. HYDRO TUBS TO BE BONDED |
|
| 10/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR ROOFTOP ONLY 1. IDENTIFY WHITE USED AS HOT 2. SECURE MC WITHIN 12" OF TERMINATIONS 3. ALUMINUM CONDUCTOR TO BE PROPERLY TERMINATED WITH INHIBITOR AND PROPER AL/CU CONNECTORS 4. PANEL DIRECTORIES TO BE CORRECTLY IDENTIFIED 5. SINGLE GROUND UNDERGROUND SCREWS 6. DISCONNECTS TO HAVE REASONABLE FRONT WORKING CLEARANCE 7. TRANSFORMERS TO BE MOUNTED IN AMBIENT TEMP. THEY ARE LISTED FOR PARTIAL INSPECTION |
|
| 08/30/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* GO THROUGH ALL UNITS BEFORE YOU CALL IN |