Permit: T06CM03977

Parcel: 10504026Q


Addresses:

4975 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
AFTER CORRECTIONS

1. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
2. LABEL UNITS OR DISCONNECTS
01/16/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PREVIOUS CORRECTIONS ARE IN PROGRESS

*NOTE: I WILL BE AWAY FROM THE OFFICE STARTING 1/19/08 AND RETURNING 2/4/08 FINAL ELECTRICAL APPROVAL WILL ONLY BE GIVEN BY ME AND WILL NEED TO WAIT FOR MY RETURN ON 2/4/08 IF CORRECTIONS ARE NOT
COMPLETED BY 1/18/08
01/15/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/14/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/10/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PARTIAL INSPECTION ONLY

INSPECTION FOR OPERATION OF EMERGENCY GENERATOR
AND ASSOCIATED EQUIPMENT

1. REVISED PLANS FOR GENERATOR SHOWS A REDUCTION IN LOADS FOR PANELS "DBE" AND "LS" BUT DOES
NOT STATE WHAT LOADS HAVE BEEN ELIMINATED -
PROVIDE CLARIFICATION
2. NEW EQUIPMENT INSTALLED AFTER INITIAL FINAL INSPECTION TO BE REVISED/INSPECTED

PARTIAL INSPECTION
3. COMPLETE ALL PRIOR CORRECTIONS
01/09/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NEED CONTRACTOR ON SITE
11/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PLANS TO BE REVISED AND APPROVE BEFORE FURTHER INSPECTIONS TAKE PLACE.
11/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) GENERATOR AND 1 LINE DIAGRAM TO BE REVISED
11/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION FOR SITE/EXTERIOR ELECTRICAL
1. PROVIDE SERVICE RECEPTACLE FOR HVAC EQUIPMENT
2. RACEWAY TO IRRIGATION CONTROL TO BE MINIMUM 18" BELOW GRADE - EMT NOT TO BE UNDER GRADE
3. FINISH ALL EXTERIOR WIRING AND FIXTURE INSTALLATION
4. POLE BASES TO BE GROUNDED WITH MIN. #10 CU GROUND, INSTALL MISSING J-BOXES COVERS
5. TEMPORARY SERVICE TO BE DE-ENERGIZED AND REMOVED
AND ASSOCIATED EQUIPMENT
6. IDENTIFY DISCONNECTS (WALK IN'S CONDENSING UNIT)
7. WIRE NUTS USED BELOW GRADE TO BE LISTED FOR WET LOCATIONS
MISC.
1. SEAL INTERIOR OF RACEWAYS INTO WALK IN'S
2. ALL PANEL DIRECTORY'S TO BE CORRECTLY IDENTIFIED
3. ONE LINE/GENERATOR PLAN TO BE REVISED & RE-APPROVED INSTALLATION NOT PER PLAN @ THIS TIME.
11/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR GENERATOR/EMERGENCY SYSTEM ONLY
PARTIAL INSPECTION

1. PLAN SHOWS 600 AMP BREAKER AT GENERATOR FOR
ATS "F" FEEDER
2. PLANS SHOW LOAD BANK FOR GENERATOR
3. PLANS DO NOT SHOW FEEDER SIZE FOR GENERATOR TO ATS "E"
4. GENERATOR SIZE IS UNDER CALCULATED LOAD FOR GENERATOR - NEC 700.5A
5. IDENTIFY ALL EMERGENCY EQUIPMENT AS COMPONENTS OF EMERGENCY SYSTEM - NEC 700.9

NOTE: HAVE SEVERAL FEEDERS/OVERCURRENT NOT PER PLAN? SINGLE LINE DIAGRAM TO BE REVISED OR INSTALL PER PLAN
11/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/05/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PARTIAL INSPECTION - OK CEILING TILES IN KITCHEN, LAUNDRY AND TELCOM ROOMS.

NOTE: REMOVE BOXES SO THEY DO NOT COVER WALK IN FAN COIL DATA PLATES
11/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR MAIN LEVEL KITCHEN ROOM #147
1. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND PROPERLY SUPPORTED @ 6' INTERVALS, SLACK WIRES USED TO SUPPORT EQUIPMENT IS TO BE SECURED @ BOTH ENDS
2. ALL 120V 15/20 AMP RECEPTACLES IN KITCHEN AREA TO BE GFI PROTECTED
3. DISCONNECT FOR DISPOSAL NEEDS PROPER FRONT WORKING CLEARANCE 36"
4. STRAP SEAL TIGHT WITHIN 12" OF TERMINATIONS
5. PANEL DIRECTORY TO BE CORRECTLY IDENTIFIED
6. SWITCH FOR DISHWASHER HOOD TO BE WEATHERPROOF
7. PROVIDE INSTALL MANUAL FOR ANSUL OTTOMAN BOX
8. BOXES CONTAINING FIRE ALARM TERMINATIONS TO BE RED
PARTIAL INSPECTION FOR THIS AREA
10/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY - AFTER HOURS INSPECTION
CHK #30313 FOR $450.00 RECEIVED

INSPECTION FOR THE INTERIOR OF FIRST AND SECOND FLOORS ONLY -
1. FINISH ALL WIRING
2. LIGHT FIXTURES, DIMMERS, EQUIPMENT TO BE PROPERLY GROUNDED
3. BOX EXTENDERS NEEDED WHERE BOX SIT BACK MORE
THAN 1/4" OR LESS THAN FLUSH TO COMBUSTIBLE SURFACE
4. OVERRIDE SWITCH FOR BATH LIGHTS NOT WORKING
5. IDENTIFY WHITE CONDUCTORS USED AS HOT
6. PROPERLY IDENTIFY ALL PANEL DIRECTORIES
7. PROPERLY SIZE EQUIPMENT GROUNDS TO
CONTACTOR J-BOXES
8. INSTALL ALL GFI BREAKERS PER PLAN
9. PROPERLY INSTALL DRYER TAILS, REMOVE BOND JUMPER
10. HYDRO TUBS TO BE BONDED
10/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR ROOFTOP ONLY
1. IDENTIFY WHITE USED AS HOT
2. SECURE MC WITHIN 12" OF TERMINATIONS
3. ALUMINUM CONDUCTOR TO BE PROPERLY TERMINATED WITH INHIBITOR AND PROPER AL/CU CONNECTORS
4. PANEL DIRECTORIES TO BE CORRECTLY IDENTIFIED
5. SINGLE GROUND UNDERGROUND SCREWS
6. DISCONNECTS TO HAVE REASONABLE FRONT WORKING CLEARANCE
7. TRANSFORMERS TO BE MOUNTED IN AMBIENT TEMP. THEY ARE LISTED FOR

PARTIAL INSPECTION
08/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
GO THROUGH ALL UNITS BEFORE YOU CALL IN