Permit: T06CM03977

Parcel: 10504026Q


Addresses:

4975 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/29/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/15/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection 1. APPLIANCES (ALL) TO BE MOUNTED IN PLACE PER MANUFACTURES INSTRUCTIONS - NEC 110.3B
2. PROVIDE GFI PROTECTION FOR ALL KITCHEN COUNTER RECEPTACLES IN REMOTE KITCHENS - NEC 210.8
3. PROVIDE GFI FOR RECEPTACLES IN SALON NEXT TO SINK

PARTIAL INSPECTION, WORK IN PROGRESS
CALL FOR FINAL WHEN REMAINDER OF REVISED PLANS ARE IN AND ALL PREVIOUS CORRECTIONS ARE COMPLETED
01/14/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/09/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/31/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
08/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK INTERIOR MAIN ENTRY AREA AND SES CORRIDOR
(140, 137, 101, 102)
08/20/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/17/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/16/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE ALL TEMPORARY WIRING THROUGHOUT BUILDING
2. CHECK SECURING/STRAPPING, KO BLANKS, ANTI-SHORT BUSHING, ETC. GO THROUGH AREA

OK WALLS ROOMS #142, 145
08/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ROOMS 14?, 149, 150 & 161
08/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOMS #152-160 EXCEPT #169
OK WALLS #147
07/31/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOMS 132, 134, 135, 138, 139, 105
07/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK KITCHEN AND DINING AREA MAIN LEVEL
07/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER
#109, #108, #107, #127, #128, #129

SERVICE - NOT READY TO INSPECT
POST BOND, PULL & TERMINATE FEEDERS (ALL),
EGRESS DOOR TO HAVE PANIC HARDWARE, PROVIDE PERMANENT ILLUMINATION
07/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ROOMS 125, 126, 110

NOTE: NEED TO POST A BOND FOR SERVICE
07/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SW STAIRWELL
07/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2ND LEVEL KITCHEN COVER
07/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK REMAINDER OF 2ND FLOOR RESIDENT ROOMS
OK N.E CORRIDOR WALLS, CEILINGS TO FIRE DOOR
CALL REMAINDER OF 2ND LEVEL COMMON AREAS WHEN READY
06/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO COVER WALLS & CEILINGS IN RMS 212, 216, 217, 218, 219, 220, 224, 225, 226
2. HALLWAYS OK - STAIRWELLS NOT READY THIS AREA
06/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ROOMS 226, 225, 224, 220, 219, 218, 217, 216, 212
FIRE ALARM BOXES, CHECK ALL KO'S
SPRAY ALL BOX ON FIRE ALARMS & SD'S RED
PLASTER RINGS MISSING
MC INSTALLED UNDER CEILING 219
MISSING RECESSED FIXTURE 217
RESUPPORT ALL LV COMM & DATA DOWN WALLS
05/31/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RMS 111-124 OK TO COVER
05/29/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ELECT. APPROVED ON 1/2 OF BUILDING EAST
END UNITS 100-118
2. COMMUNICATIONS WIRING DENIED, COMMUNICATIONS WIRING PER NEC 800.6 HAS TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER - PROPERLY SUPPORTED AND PHYSICALLY PROTECTED PLASTIC GROMMET MISSING IN SOME AREAS, WIRING OUTSIDE OF STUD AREA - KEEP AWAY FROM METAL SHARP EDGES
REVISE AND RECALL
05/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH ELECT RMS 111-124
1. SW GEAR ROOM REQUIRES EITHER 6' IN FRONT OF WITH 1 DOOR OR 2 EXITS - ONE AT EACH END -- 2002 NEC 110.26 C-2
2. LETTER ON MC-AP
PER EE OK, ON INTERCHANGE COPPER FOR AC
LETTER NEEDS TO BE SPECIFIC ON SIZES INTERCHANGED.
3. MUD RINGS ON CATV - OK (OUTLETS)
4. RM 111 THRU 124 OK TO COVER (NO STAIRWAYS)
5. CALL MONDAY FOR DATA INSTALLATIONS FOR 5/29/07
05/21/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
JOHN - ELECTRICAL FOREMAN (631-1040)
05/18/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NO INSPECTION AT THIS TIME
1. WIRING NOT PER PLAN -- PROVIDE A LETTER FROM THE ELECTRICAL ENGINEER OF RECORD STATING THAT THIS SPECIFIC TYPE OF MC IS ACCEPTABLE AND THAT NOTES 3, 4, 14, 19 DO NOT NEED TO BE FOLLOWED. LETTER TO BE STAMPED BY HIM AND SPECIFICALLY REFERENCE THE MANUFACTURER AND PART # OF MC TYPE USED.
05/03/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY
1. PROVIDE MC LISTING INFORMATION AS TO HOW IT IS LISTED TO BE USED.
2. PROVIDE BACK SUPPORT FOR RECEPTACLE BOXES AS NEEDED.
3. PROVIDE LETTER FROM ARCHITECT FOR USE OF MC
4. FINISH ALL MAKE
5. MC NOT TO BE BUNDLED MORE THAN 24" WITHOUT DERATING -- NEC 310.15