Permit: T06CM03977

Parcel: 10504026Q


Addresses:

4975 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
01/29/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
10/09/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK TO POUR POLE BASES AS REQUIRED
NO GROUNDING ELECTRODE REQUIRED ON PLAN
04/02/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE LIGHT RACEWAYS GENERATOR AREA, ELEVATOR ROOM, FLOOR BOX 1ST LEVEL

STAY 24" MIN. DEPTH FOR ALL RACEWAY WITH TRAFFIC AREA OK TO CONTINUE.
03/23/2007 ELECTRIC - UNDERGROUND Partial Approval OK TO COVER GENERATOR FEEDERS, BRANCH CKT RACEWAYS TO CURB @ GENERATOR LOCATION
OK FEEDER RACEWAY CONTINUATION SERVICE
TO FIRST POUR STUBOUT
03/19/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK SERVICE SECONDARY RACEWAY COVER
INSTALL WARNING RIBBON
WHEN YOU BACKFILL -- NEC 300.5
03/06/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK RACEWAY COVER UNDER SLAB LINES SS-GG

NOTE:
UFER FOR SES NOT APPROVED
WILL NEED INSPECTION/APPROVAL BEFORE COVER
02/13/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
INSPECTION MADE 2/9/07
02/09/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
NOT SURE WHAT TO INSPECT
SUPER/ELECTRICIAN NOT ON SITE, NO PLANS
OK TO COVER RACEWAYS TO N.E SIDE ELECTRICAL ROOM
STUB FOR FIRST POUR