Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 10/09/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO POUR POLE BASES AS REQUIRED NO GROUNDING ELECTRODE REQUIRED ON PLAN |
|
| 04/02/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK POLE LIGHT RACEWAYS GENERATOR AREA, ELEVATOR ROOM, FLOOR BOX 1ST LEVEL STAY 24" MIN. DEPTH FOR ALL RACEWAY WITH TRAFFIC AREA OK TO CONTINUE. |
|
| 03/23/2007 | ELECTRIC - UNDERGROUND | Partial Approval | OK TO COVER GENERATOR FEEDERS, BRANCH CKT RACEWAYS TO CURB @ GENERATOR LOCATION OK FEEDER RACEWAY CONTINUATION SERVICE TO FIRST POUR STUBOUT |
|
| 03/19/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK SERVICE SECONDARY RACEWAY COVER INSTALL WARNING RIBBON WHEN YOU BACKFILL -- NEC 300.5 |
|
| 03/06/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK RACEWAY COVER UNDER SLAB LINES SS-GG NOTE: UFER FOR SES NOT APPROVED WILL NEED INSPECTION/APPROVAL BEFORE COVER |
|
| 02/13/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* INSPECTION MADE 2/9/07 |
|
| 02/09/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* NOT SURE WHAT TO INSPECT SUPER/ELECTRICIAN NOT ON SITE, NO PLANS OK TO COVER RACEWAYS TO N.E SIDE ELECTRICAL ROOM STUB FOR FIRST POUR |