Permit: T06CM03969

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/23/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/10/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WALLS AND HARD LIDS.
08/09/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. STRAP ALL MC WITHIN 12" OF BOX ENTRY
2. GROUND ALL BOXES
3. PROVIDE MUD RINGS FOR ALL BOXES
4. PROVIDE ADDITIONAL BRACE/SUPPORT FOR BOXES MOUNTED ON STEEL STUDS THAT ROLL INTO WALL
(BACK BRACE)
5. SEAL UNUSED OPENINGS IN BOXES
6. WIRING LOOKS INCOMPLETE