Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/13/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* YOU NEED TO SEPARATE HOT AND COLD PIPING ON NORTH END. ALSO SEE SPEC #4 PIPES ARE SOLDERED TOGETHER. AFTER SEPARATIN, INSTALL PIPE INSULATION AND LABELS ACCORDING TO SPECIFICATIONS #14 AND #18 RECALL TO HAVE INSPECTED AFTER COMPLETING. |
|
| 02/06/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SEPERATE HOT AND COLD WATER PIPING 2) USE PIPE SUPPORTS NOT TIE WIRE 3) SAFETY PLATES NEEDED ON DRAIN AND VENT PIPING. ALSO HB FLUX ON PIPING. REMOVE W/ DAMP RAG. 4) HW NO TIED IN 5) CW VALVE IS OFF 6) PIPING IS NOT UNDER TEST 7) LIVE ANGLE STOPS IN WALL-PERM CAP 8) TEST ON DWV IS OK 9) POST ADDRESS, EVEN IF TEMPORARY |
|
| 02/01/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) SWEEPS REQUIRED ON TRAP ARMS 2) TEST REQUIRED 3) SAFETY PLATES REQUIRED 4) RFEMOVE EXCESS FLUX FROM COPPER JOINTS 5) ALL COPPER TUBING SHALL BE ? TO THE FULL ID OF THE TUBE |
|
| 12/21/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |