Permit: T06CM03966

Parcel: 13316027S


Addresses:

2050 N WILMOT RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/01/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
02/13/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
YOU NEED TO SEPARATE HOT AND COLD PIPING ON NORTH END. ALSO SEE SPEC #4
PIPES ARE SOLDERED TOGETHER.
AFTER SEPARATIN, INSTALL PIPE INSULATION AND LABELS ACCORDING TO SPECIFICATIONS #14 AND #18
RECALL TO HAVE INSPECTED AFTER COMPLETING.
02/06/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SEPERATE HOT AND COLD WATER PIPING
2) USE PIPE SUPPORTS NOT TIE WIRE
3) SAFETY PLATES NEEDED ON DRAIN AND VENT PIPING. ALSO HB FLUX ON PIPING. REMOVE W/ DAMP RAG.
4) HW NO TIED IN
5) CW VALVE IS OFF
6) PIPING IS NOT UNDER TEST
7) LIVE ANGLE STOPS IN WALL-PERM CAP
8) TEST ON DWV IS OK
9) POST ADDRESS, EVEN IF TEMPORARY
02/01/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SWEEPS REQUIRED ON TRAP ARMS
2) TEST REQUIRED
3) SAFETY PLATES REQUIRED
4) RFEMOVE EXCESS FLUX FROM COPPER JOINTS
5) ALL COPPER TUBING SHALL BE ? TO THE FULL ID OF THE TUBE
12/21/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*