Permit: T06CM03966

Parcel: 13316027S


Addresses:

2050 N WILMOT RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
12/21/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
12/19/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. SANITARY TEES ARE TO BE INSTALLED IN THE VERTICAL POSITION.
2. USE PROPER WYE PATTERN FITTING FOR GT VENT (TRY A WYE AND 1/6TH BEND)
3. CORRECT BACK PITCH ON GT VENT INSIDE BUILDING.
4. RETEST GT WASTE & VENT AFTER CORRECTING.
5. SANITARY DRAINAGE IS OK
12/04/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. TEST TO BE IN PLACE ON ALL PIPING AT TIME OF INSPECTION.
2. YOUR FLOW CONTROL SHALL BE INSTALLED PER PLAN WITH CORRECT VENTING. ON GREASE WASTE IN TAILPIECE OF FIXTURE.
3. FLOW CONTROL TO BE SAME SIZE AS DRAINAGE (CANNOT PROVIDE 3" FLOW CONTROL ON 2" DRAIN PIPING).
4. PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR VENT BELOW FLOOD RIM OF FIXTURE.

SANITARY 2" DRAINAGE WATER TEST UNDERGROUND ONLY WITH PIPE WRAPS OK

5. CANNOT REVENT BELOW FLOOD RIM OF FIXTURE.
6. SHALL PROVIDE MINIMUM 2% FALL ON GREASE DRAINAGE.
11/15/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :$
I WAS UNABLE TO LOCATE
CONTRACTOR NEEDS TO POST ADDRESS
CONTRACTOR MAY PROVIDE A CONTACT NUMBER.