Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/12/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) SEPERATE PARALLEL GROUND PATHS 2) USE SPLIT BOLT LISTED FOR COOPER AND ALUMINIUM 3) ONLY ONE GROUND PER TERMINAL/LUG 4) FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH NON COMBUSTIBLE PRODUCT 5) NEED GAS BOND |
|
| 01/11/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* NO GROUNDING SYSTEM NO TERMINATIONS DONE YET |