Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 08/03/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE A TRAP ON CONDENSATE DRAIN |
|
| 07/28/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* THE CONDENSATE DRAIN CANNOT TERMINATE DIRECTLY INTO A SEWER VENT. LEFT GAS CLEARANCE CARD |
|
| 07/25/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 15 PSI TEST IS OK SUPPORT THE ELEC. DISCONNECT ON ROOF SUPPORT THE GAS LINE ON ROOF CONDENSATE CANNOT TERMINATE INTO THE SCUPPER AND CANNOT DRAIN ONTO A HARD SURFACE. PAINT EXPOSED PVC W/LATEX PAINT. BLOCK & CLAMP EVERY 4'. NEED TO SEE THE NEW DRYER VENT THAT WAS INSTALLED. |