Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/31/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - ABS DWV OK - INSTALL FD, PROVIDE PIPE WRAPS RECALL FOR INSPECTION PRIOR TO CONCRETE. - EXISTING TOILET RMS OK TO COVER - WH ABOVE CEILING REQUIRES A DRAIN PAN W/SEPARATE DRAIN. - ALSO WH CANNOT BE THE ONLY TEMPERATURE CONTROL FOR LAVITORIES. - OK TO COVER WALL EXCEPT AT RELOCATE SINK IN RM 109, PLAN REQUIRES 3/4" SUPPLY |