Permit: T06CM03944

Parcel: 11516025C

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM03944

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/15/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/31/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- ABS DWV OK
- INSTALL FD, PROVIDE PIPE WRAPS RECALL FOR INSPECTION PRIOR TO CONCRETE.
- EXISTING TOILET RMS OK TO COVER
- WH ABOVE CEILING REQUIRES A DRAIN PAN W/SEPARATE DRAIN.
- ALSO WH CANNOT BE THE ONLY TEMPERATURE CONTROL FOR LAVITORIES.
- OK TO COVER WALL EXCEPT AT RELOCATE SINK IN RM 109, PLAN REQUIRES 3/4" SUPPLY