Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 10/03/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) RETRO FOR SHEARWALL HOLDOWNS GARAGE 2) OK TO CONTINUE ON OUTSIDE WALLS |
|
| 09/28/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) OK TO COVER OUTSIDE SHELL 2) STILL WAITING ON RETRO'S FOR HOLDOWNS 3) SHIM CUT 2 X 6 AT SHEARWALL 4) SHEAR TRANSFER AT INTERIOR GARAGE SHEARWALL NEEDS A.35 4' ON CENTER |
|
| 09/22/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RETRO HOLDOWNS 3 IN FRONT, 2 IN BACK 2) REPLACE CUT 2 X 6 AT INTERIOR GARAGE SHEAR 3) VERTICAL BLOCKS REQUIRED UNDER OUTSIDE WALLS OF ENTRY OVERHANG PER 15/DT1 4) HINGE BRACING REQUIRED 48" ON CENTER PER 6/DT1 5) TIE ENTRY TRUSSES TO INTERIOR BEARING WALL 6) 8D NAILS REQUIRED IN BIRD BOARDS 7) NAIL HINGE BRACE BLOCKS THROUGH SHEATHING 8) 3 KING STUDS REQUIRED AT GARAGE HDR 9) STRAP GARAGE HDR PER PLAN 10) SHEAR TRANSFER AT INTERIOR GARAGE SHEARWALL |