Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM03927
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/01/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED HEATER KITCHEN MODEL USED MARKED ON HEADER TO COMPLETE FUSE SIZES 2) A/C DISCONNECT FUSES ARE OVER SIZED 3) NON GFI OUTLET ON EAST GARAGE WALL, MUST BE MONO OUTLET OR BE MADE GFI |
|
| 04/25/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) A/C AND FURNACE NOT FUSED 2) EXTERIOR AND GARAGE OUTLETS NOT GFI PROTECTED 3) HALL SMOKEY DOES NOT SET OFF OTHER SMOKIES 4) EAST COUNTER TOP NEEDS OUTLET BETWEEN 0"-24" FROM THE SOUTH END OF COUNTER 5) DISHWASHER DRAIN MUST LOOP UP TO BOTTOM OF COUNTER |
|
| 04/24/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE PRESENT FOR ACCESS-7:45 AM 2) MESSAGE COULD NOT BE RETRIEVED-COMPUTER DOWN 3) PLEASE RECALL |