Permit: T06CM03925

Parcel: 10604070A


Addresses:

3533 N FONTANA AV

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/27/2007 FRAMING Approved IVRS - Inspection :*
06/26/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FHA STRAPS AT LAUNDRY ROOM REQUIRED 8 NAILS EACH SIDE OF EACN STRAP-DUE TO OVER KNOTCHED TOP PLATE
2) FILL GAP AT SIDE DOOR ENTRY WITH 2 X FOR STUCCO MESH
3) CUT EXCESS WIRE AT MICROWAVE OUTLET KITCHEN
4) WATER SUPPLY LINE-HALL BATH TO TOILET RELOCATE-PROTECT FROM DRYWALL
5) WHEN YOU CALL BACK FOR RE-INSPECTION LEAVE ME A MESSAGE OR CALL ME, SO I CAN MEET YOU IN THE MORNING
06/21/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROTECTION PLATE ON VTR 2" AT KITCHEN
2) NEED PROTECTION PLATES ON VENT LINE AND WATER LINES WHEN IT HAS LESS 1 1/4 FROM EDGE OF STUD TO EDGE OF HOLE
3) NEED TO PROTECT CONDUCTORS AT HOMERUN PANEL COMING THRU WALL
4) NEED TO SEAL AROUND OUTLET BOX REAR OF HOUSE AND LIGHT OUTLET FRONT OF HOUSE
5) SEAL ALL OVERSIZED OPENING AT TOP PLATES
6) REPLACE 2 X 6 ON EXT WALL WERE OVER KNOTCHED PER CODE AND REPLACE
7) STOPPED INSPECTION-NOT READY
06/06/2007 FRAMING Cancelled IVRS - RI canceled