Inspection History Details
Inspection Status: Cancelled
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2007 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
| 02/01/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/29/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DRY OFF ALL PIPES TO CHECK FOR LEAKS 2) VENT WYES MUST BE IN UPPER SECTION OF HORIZONTAL LINES 3) PROVIDE 1/4" PER FOOT OF FALL IN ALL HORIZONTAL DRAINS 4) REMOVE BACK TO BACK CLEANOUTS 5) WATER LINES MUST BE SIZED PER PLAN 6) LEAK UNDER M. BATH TUB 7) VENT REQUIREMENTS NOT PER PLAN OR UPC |
|
| 01/22/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/08/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |