Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
11/20/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
08/29/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) ITEM 5 OF 8/24/06 NOT DONE
2) OK TO DRY IN
08/24/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHEAR WALLS NOT BUILT PER NOTE 6 SHEARWALL SCHEDULE
2) NO TRUSS DRAWINGS ON SITE
3) GABLE END TRUSSES NOT CLIPPED PER 1/SD3
4) BLOCK AND NAIL ALL SHEAR PANEL ENDS AND EDGES PER PLAN
5) NORTH WEST HOLDOWN NOT ON FULL LENGTH DBL STUDS AND SPAULED. PROVIDE ENGINEER OF RECORD APPROVED REPAIR
6) SOUTH SHEAR NOT NAILED
7) ROOF OK TO DRY IN