Permit: T06CM03913

Parcel: 10511061L


Addresses:

4470 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/29/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
CORRECTIONS FROM PREVIOUS INSPECTION HAVE NOT BEEN COMPLETED. ALSO, REMOVE CONDUCTORS FROM UNUSED FLOOR BOX, PROVIDE 12' MIN. LADDER FOR INSPECTION.
IF ALL NOT COMPLETE NEXT TIME, A REINSPECTION FEE WILL BE CHARGED.
09/21/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROVIDE FIXTURE SUPPORT IN CEILING GRID PER NEC/NEED SUPPORT WIRE @ EACH END & TO STRUCTURE.
2. SUPPORT/SECURE MC AS REQUIRED - NEC 300.11 IN CEILING
3. STRAP MC WITHIN 12" OF TERMINATIONS
4. SEAL UNUSED OPENINGS IN FIXTURES & J-BOXES
5. USE EQUIPMENT GROUND TO GROUND ALL FIXTURES & J-BOXES
6. MC SLOPPY IN CEILING
7. FLOOR RECEPTACLE COVERED BY NEW WALL
8. PROVIDE LADDER FOR CEILING ACCESS
9. CORRECTLY IDENTIFY CKT'S IN PANEL DIRECTORY.