Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* CORRECTIONS FROM PREVIOUS INSPECTION HAVE NOT BEEN COMPLETED. ALSO, REMOVE CONDUCTORS FROM UNUSED FLOOR BOX, PROVIDE 12' MIN. LADDER FOR INSPECTION. IF ALL NOT COMPLETE NEXT TIME, A REINSPECTION FEE WILL BE CHARGED. |
|
| 09/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROVIDE FIXTURE SUPPORT IN CEILING GRID PER NEC/NEED SUPPORT WIRE @ EACH END & TO STRUCTURE. 2. SUPPORT/SECURE MC AS REQUIRED - NEC 300.11 IN CEILING 3. STRAP MC WITHIN 12" OF TERMINATIONS 4. SEAL UNUSED OPENINGS IN FIXTURES & J-BOXES 5. USE EQUIPMENT GROUND TO GROUND ALL FIXTURES & J-BOXES 6. MC SLOPPY IN CEILING 7. FLOOR RECEPTACLE COVERED BY NEW WALL 8. PROVIDE LADDER FOR CEILING ACCESS 9. CORRECTLY IDENTIFY CKT'S IN PANEL DIRECTORY. |