Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 10/05/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE FOAM PIPE WRAPS ON PIPING PENETRATING SLAB. |
|
| 10/04/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
| 09/29/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PLEASE READ NOTES FROM PREVIOUS INSPECTIONS. - INSTALL FULL SIZE CLEANOUT ON SEWER, TEST. - PROVIDE UNIFORM SLOPE ON 3" SEWER. - CONNECT SEWER TO HCS AND CALL FOR INSPECTION. - ADHESIVE TAPE IS NOT ALLOWED ON PEX, USE ZIP TIES. - REMOVE ROCKS FROM AROUND PEX, SUPPORT PEX IN ALL AREAS. - TEST, CALL FOR INSPECTION. |
|
| 09/26/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* ROUGH SOIL PIPING WITHIN BUILDING IS OK TO COVER. |
|
| 09/25/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. YOUR WATER TEST IS DOWN 2. YOUR TRANSITION COUPLING AT HCS CONNECTION IS UNDER STRESS, ASSURE PROPER ALIGNMENT. 3. PROVIDE A 4" CLEANOUT TO SERVE 4" SEWER. 4. TYPE L COPPER REQUIRED AT TRANSITION RISER. 5. JOINTS IN WATER PIPING SHALL BE UNDER TEST FOR INSPECTION. 6. CALL IN FOR INSPECTION; YARD WATER AND HCS, IF YOU WOULD LIKE TO HAVE THESE ITEMS INSPECTED. |