Permit: T06CM03904

Parcel: 119031360


Addresses:

750 W 41ST ST

Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
12/06/2006 SHEET ROCK NAILING Approved IVRS - Inspection :*
12/05/2006 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE DRYWALL ON POTENTIAL DAMAGE BY STAPLES ON PLUMBING AND ELECTRICAL AREAS.
2. AFTER STUCCO MESH APPROVAL SHEETROCK
NAILING INSPECTION
ABOVE CEILING INSPECTION FIREWALL NEED TO PROVIDE FIRE SEALANT ON ALL PENETRATIONS.
12/01/2006 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLASTER RINGS NOT ALLOWED IN FIRE BARRIER
2. PROVIDE ACCESS FOR ABOVE CEILING
11/30/2006 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE LEFTOVER PIECES ON WALL FOR NAILING VERIFICATION.
2. PROVIDE ATTIC ACCESS AND ACCESSIBILITY FOR FIREWALL INSPECTION ABOVE CEILING.
3. PROVIDE ACCESSIBILITY FOR INSPECTION ON NORTH BUILDING.

NOT APPROVED FOR TAPE OR PLASTER INSTALLATION BEFORE 1045 SHEETROCK NAILING APPROVED.