Permit: T06CM03885

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
09/02/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
07/16/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
05/19/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK J-BOXES & LIGHT POLES AT BRIDGES
04/18/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) CONTR. REQUEST AFTER HOURS RETURN INSP, $150.00 FEE PAID CHECK #382481
04/18/2008 ELECTRIC - UNDERGROUND Partial Approval - INSTALL GROUNDING ELECTRODE SYSTEM
- CONDUIT FEEDERS INTO CABINET TO HIGH,
CODE ALLOWS 3" MAX.
04/11/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
COULD NOT LOCATE MATT
03/28/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE BASES AT BRIDGES
03/20/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE BASES AS DISCUSSED
03/03/2008 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
There is no access to the site.| 920*
CALLED CONTRACTORS OFFICE 3:45 AND SAID I WAS WORKING LATE -- NOBODY ON SITE 5:15
02/26/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK AS MARKED ON FIELD PLANS AND POLE BASES AT HARKINS ENTRANCE
02/21/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
CONTACT MATT @ 370-2008

OK U.G AS PER MARKED FIELD PLANS
02/20/2008 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
COULD NOT LOCATE CONTR. NO CONTACT PH# LEFT AS REQUESTED - RECALL INSP.
02/15/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G AND POLE BASES AS MARKED ON FIELD PLANS
01/31/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
- OK SITE LIGHTING U.G AS MARKED ON PLAN
- OK SECONDARYS U.G FOR SERVICE
01/23/2008 ELECTRIC - UNDERGROUND Partial Approval OK PARTIAL AS MARKED & INITIALED ON FIELD PLANS
01/18/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. CONDUITS OR DESIGN FOR SERVICE SECONDARYS FOR SERVICES TO BLDS. THIS SITE NOT ON PLANS, PROVIDE APPROVED PLANS FOR SECONDARYS INSTALLED UNDER THIS ACTIVITY.
2. OK PARTIAL PARKING LTG. CONDUITS AS MARKED & INITIALED ON FIELD PLANS AT BEST BUY & PENNY'S AREA
3. PROVISIONS IN 310-15B MAY BE APPLICABLE WHERE MULTIPLE RACEWAYS ARE INSTALLED CLOSE TOGETHER.
01/17/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
RECALL INSP. LEAVE PH# ON MESSAGE
PLASE TALK SLOW & CLEAR WHEN LEAVING MESSAGE
01/09/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 1 1/4" U.G CONDUITS FOR WALL SIGNAGE
ALONG CALLE SANTA CRUZ
11/27/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK U.G. PVC AS MARKED ON PLAN
10/29/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
- OK PVC U.G BETWEEN POLE BASES AS MARKED ON FIELD PLANS, MATT IS THE CONTACT PERSON 370-2008
- BE ADVISED, ROCKS MAY DAMAGE CONDUITS 300.5
10/24/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The inspector was unable to locate the job.| 945$
PLEASE RESCHEDULE INSP. LEAVE PH. # OF CONTACT PERSON