Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM03884
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | ||
01/05/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 2/D6 BLOCKING IN KITCHEN/DINING AREA NOT DONE 2) OK TO DRY IN AND LATHE EXTERIOR |
|
12/08/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | 1) ITEM 2/D6 BLOCKING IN KIT/DINING AREA NOT DONE 2) MISSING NAILING SHEAR TRANSFER 5/D3 3) EDGE BLOCKING HAS STAPLES INSTEAD OF NAILS 4) A03 TRUSSES NEED RAT RUN |
|
12/01/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NO TRUSS DRAWINGS ON SITE 2) NO OSHA APPROVED LADDER ACCESS TO ROOF 3) NAIL OSB SHEAR TO SAME DBL STUDS THAT THE HOLDOWNS ARE CONNECTED TO 4) CLIP TOP AND BOTTOM OF ALL BUILT UP POSTS 5) GARAGE SHEARWALL 3 MUST BE 12 FEET LONG 6) GARAGE PAHD 42 SOUTH WALL WRONG LOCTATION. PROVIDE ENGINEERS APPROVED AND CITY OF TUCSON APPROVED REPAIR 7) STUDS WITH CS20 STRAP CONNECTIONS MUST BE CLIPPED TOP AND BOTTOM 8) 2/?2 KNEE BRACES NOT INSTALLED 9) NOTE 28 POSTS NOT INSTALLED 10) STOPPED INSPECTION-TOO MANY ITEMS |