Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2006 | ELECTRIC - FINAL | Approved | ||
| 12/08/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLANS SHOW BATH GFI? EVAP COOLER BOX? 2. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED -- NEC 408.4 3. EMERGENCY LIGHTING TO BE ON CKT FOR LIGHTING IN THAT AREA -- NEC 700.12(E) AND AIM DOWN & OUT. 4. REMOVE CEILING TILES FOR INSPECTION OF CEILING. 5. HAVE OPEN MC ABOVE BATHROOM. 6. IDENTIFY ALL WHITE CONDUCTOR USED AS HOT -- NEC 200 7. MC TO BE SECURED WITHIN 12" OF TERMINATION -- NEC 330.30 8. SUPPORT MC OFF GRID -- NEC 300.11 9. SECURE FIXTURES TO GRID -- NEC 300.11 10. NEED SUPPORT WIRES ON ALL CEILING FIXTURES IN GRID NEC 300.11 11. NEED DISCONNECT FOR INSTA-HOT -- NEC 422.31 (B) 12. PROVIDE ROOFTOP SERVICE RECEPTACLE -- NEC 210.63 |
|
| 11/29/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |