Permit: T06CM03882

Parcel: 10612017R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/21/2006 ELECTRIC - FINAL Approved
12/08/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLANS SHOW BATH GFI? EVAP COOLER BOX?
2. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED -- NEC 408.4
3. EMERGENCY LIGHTING TO BE ON CKT FOR LIGHTING IN THAT AREA -- NEC 700.12(E) AND AIM DOWN & OUT.
4. REMOVE CEILING TILES FOR INSPECTION OF CEILING.
5. HAVE OPEN MC ABOVE BATHROOM.
6. IDENTIFY ALL WHITE CONDUCTOR USED AS HOT -- NEC 200
7. MC TO BE SECURED WITHIN 12" OF TERMINATION --
NEC 330.30
8. SUPPORT MC OFF GRID -- NEC 300.11
9. SECURE FIXTURES TO GRID -- NEC 300.11
10. NEED SUPPORT WIRES ON ALL CEILING FIXTURES IN GRID
NEC 300.11
11. NEED DISCONNECT FOR INSTA-HOT -- NEC 422.31 (B)
12. PROVIDE ROOFTOP SERVICE RECEPTACLE -- NEC 210.63
11/29/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*