Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM03860
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
09/13/2006 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) SECURE GAS LINE 2) 3/8" PEX 12.0 LINE 12" FROM PEX KITCHEN CEILING 3) REAR WALL 2" DRAIN CHECK FOR STAPLE 4) ? NAILS IN HANGERS AT GIRDER ROOF USE SINKER 2 1/2 TECO NOT LOGN ENOUGH 5) BRING GIRDER POST PT LOADS DOWN TO CONCRETE INCLUDE FLOOR SPACE 6) ABOVE STAIR SPLICE TOP PLATE NOT WRAPPED 7) NAIL ALL SHEAR PLATES, 6" ON CENTER & 12" ON CENTER NON-SHEAR 8) 2ND FLOOR EXHAUST FAN NOT SECURED, 2ND BATH DUCT DAMAGED 9) RETURN DUCT HALL NOT SECURED, CHECK ALL RETURNS 10) 50 PSI AIR TEST REQUIRED POT H20 11) PLAN CALLS FOR GLTS HANGER IN GARAGE GLU LAM TO LAM 12) HUS TYPE INSTALLED VERIFY, IF EQUAL OR BETTER |