Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM03856
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/07/2007 | FRAMING | Approved | IVRS - Inspection :* | |
02/06/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEM 11 STILL NOT CORRECTED 2) THIS INSPECTION HAS NOT BEEN MET AND A REFEE WILL BE IMPOSED FOR NEXT TIME |
|
01/26/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* ITEM #4, 10, 11 NOT CORRECTED |
|
01/24/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRESTOP B-VENT 2) H.D. UNDER STAIRWAY WRONG LOCATION 3) FIRESTOP AT CHASE S.E. BEDROOM 4) FIRESTOP UNDER TUB-HALL BATH AND CHASE 5) MISSING PIECE OF LATHE AT ENTRY DOOR 6) NOT COMPLETE AT ROOF VENT BACK 7) SEAL ALL PENETRATIONS-BACK OF HOUSE 8) B-VENT NEEDS TO BE LOCATED IN ORDER TO MAKE PROPER CONNECTION TO H20 HEATER 9) A/C LINE BEDROOM NEEDS PROTECTION STRAP 10) INSTALL GAS BOND 11) SHEAR TRANSFER ON SHEARWALL 2ND FLOOR NOT PER DRAWING 5/D3, IF YOUR GOING TO USE 2 X 4 NEED TO LOOK AT 1/D3 |