Permit: T06CM03856

Parcel: 141331040


Addresses:

8416 S EGYPTIAN DR


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM03856

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2007 FRAMING Approved IVRS - Inspection :*
02/06/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEM 11 STILL NOT CORRECTED
2) THIS INSPECTION HAS NOT BEEN MET AND A REFEE WILL BE IMPOSED FOR NEXT TIME
01/26/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
ITEM #4, 10, 11 NOT CORRECTED
01/24/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIRESTOP B-VENT
2) H.D. UNDER STAIRWAY WRONG LOCATION
3) FIRESTOP AT CHASE S.E. BEDROOM
4) FIRESTOP UNDER TUB-HALL BATH AND CHASE
5) MISSING PIECE OF LATHE AT ENTRY DOOR
6) NOT COMPLETE AT ROOF VENT BACK
7) SEAL ALL PENETRATIONS-BACK OF HOUSE
8) B-VENT NEEDS TO BE LOCATED IN ORDER TO MAKE PROPER CONNECTION TO H20 HEATER
9) A/C LINE BEDROOM NEEDS PROTECTION STRAP
10) INSTALL GAS BOND
11) SHEAR TRANSFER ON SHEARWALL 2ND FLOOR NOT PER DRAWING 5/D3, IF YOUR GOING TO USE 2 X 4 NEED TO LOOK AT 1/D3