Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM03856
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* 1) ENGINEERED REPAIR IN FILE |
|
12/06/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) A05 TRUSS FRONT BROKEN, LOOK FOR MARKED ON FLOOR 2) TWO NAILS IN ALL WIND BRACES AT PLATES 3) ALL P.A.'S WRONG SIZE 16D'S |
|
12/04/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RSP4 CLIP AT CORNERS 2) RSP4 CLIPS ON STUDS WITH COIL STRAPS 3) PROTECTION PLATE NORTH BOTTOM PLATE FOR PLUMBING 4) DBL STUD AT SHEAR PANEL CORNER N.W. 2ND FLOOR 5) 2 A34 AT PATIO JOIST 6) DBL STUD SHEAR PANEL CORNER S.W. 1ST FLOOR 7) GLU LAM NEEDS 2 H2.5 CLIPS 8) TRUSS BLOCKING IN KITCHEN AND DINING ROOM NOT PER 2/D6 9) NO ACCESS TO ROOF NAILING |