Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/13/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 09/12/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. MAST (BOTH) FOR SERVICE NEEDS TO BE BONDED -- NEC 250.92 2. WATER & EQUIPMENT BONDING CONDUCTORS ARE UNDERSIZED -- NEC 250.104 & 250.102 C |