Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM03849
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
12/06/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING NAILING ON NORTH SIDE ROOF 2) DBL NAIL STRISS ATTACHED TO SHEAR (DRAG TRUSS) 3) TWO NAIL IN ALL WIND BRACES AT PLATES 4) WRONG SIZE NAILS IN P.A.'S |
|
12/04/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO LADDER 2) H.D. SOUTH EAST REAR OF BLDG MISSING SHEAR PANEL 3) C.S. STRAPS GLU-LAM BEAM ? ON COLUMNS 4) MISSING LTHJ HANGERS GARAGE 5) RSP4 CLIPS MISSIGN BALLOON WALLS 6) SHEAR TRANSFER ON 2ND FLOOR NOT NAILED CORRECTLY 7) NO TRUSS CALCS |