Permit: T06CM03840

Parcel: 11711014A


Addresses:

197 N CHURCH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM03840

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/06/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/21/2007 ELECTRIC - FINAL Partial Approval OK FOR TEMP C OF O

1. CONTRACTOR WORKING ON FINISH OF LOW VOLTAGE INSTALLATION -- RESTROOM AREA -- CALL FOR FINAL
2. FINISH INSTALLATION OF ALL DEVICE COVERS
3. AREA OF OPEN TRENCHING AT SERVICE TO BE BARRICADED AND GATE CLOSED OFF TO PROHIBIT ENTRY
05/17/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OFFICES
1. LABEL OUTSIDE OF PANEL PERMANENTLY
2. LIGHTING IN FRONT OFFICE - CORD CANNOT PASS THROUGH
WOOD CEILING -- SEE INSTRUCTIONS & PROVIDE.
3. ALL DEVICE COVERS TO BE INSTALLED.
4. EXPOSED CONDUCTORS ON PORCH FOR LIGHTING - KNOB & TUBE TYPE WIRING METHOD TO OUTDATED TO BE USED.

RESTROOMS:
1. IN BETWEEN BATHROOM ARE DEVICE COVERS MISSING, LABEL O/S OK PANEL
2. KNOCKOUTS MISSING ON LOW VOLTAGE EQMT.
3. SECURITY & PHONE SYSTEMS NOT FINISHED.
4. LOW VOLTAGE FIXTURE O/S MISSING.

SERVICE:
1. LABEL CIRCUITS PERMANENTLY
2. COVER UNDERGROUND

SOLDIERS BARRACKS:
1. LIGHTING NOT FINISHED
2. SCRAPE PAINT BEHIND SCREW (GROUND) A - GUTTER
04/25/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FINISH ALL TRIMS, LIGHTING, RECEPTACLE, POWER DEVICES
2. LABEL PERMANENTLY ALL PANELS, SERVICE, CIRCUIT BREAKERS.
3. WILL TEST ALL EM LIGHTING, GFI PROTECTED
CIRCUITS, ETC
4. MAIN TO PNL AT RESTROOM TO BE PULLED
5. COMPLETE OUTDOOR LIGHTING & COVER ALL JUNCTION BOXES.