Permit: T06CM03840

Parcel: 11711014A


Addresses:

197 N CHURCH AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06CM03840

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
MOVE CIR. 23 FROM WALL TO NORTH PATIO WALL
OK ROUGH
03/09/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
BEHIND TRIPLEX
03/02/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. UNDERGROUND OK 2 GROUND RODS TO TRIPLEX PNL
2. ABOVE CEILING OK COMMISSARY
02/26/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK UNDERGROUND TRIPLEX
02/20/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK UNDERGROUND BETWEEN BLDG C TO TRIPLEX
02/13/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
MUNITIONS BLD PANEL -- OK RISERS & COMMUNICATIONS
OK #4CU UFER TO REBAR
02/08/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK UNDERGROUND BLDG C
2) OK SOUTH WOOD WALL IN PATIO
01/18/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK TO COVER AREA #1 CONCRETE COVERED
01/10/2007 ELECTRIC - UNDERGROUND Partial Approval 1. OK TO COVER TRENCH BETWEEN PNL C & D NEED TO COVER EXCEPT POWER CONDUIT FEEDER AND BRANCH CONDUITS TO BE 18" DEEP OR COVER WITH CONCRETE 2" MIN.
RIGID CONDUIT OK AT 6" DEEP.
2. CONDUITS BETWEEN BATHROOMS & STREET SCOPE NEED TO ALSO BE 18" DEEP, EXPOSE ENDS AND VERIFY GRADE LEVEL.