Permit: T06CM03836

Parcel: 141015530

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T06CM03836

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2008 BUILDING - FINAL Approved IVRS - Inspection :*
07/16/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) BROKEN INSULATION ON ALL FEEDER SERV. TAPE
2) REDUCE BREAKERS ON A/C TO WIRE DIAMETER A/C LABEL EXAMPLE 50/50 #8 AC 30 AMP CIRCUIT
3) MARK FUSE SIZE GARAGE UNITS 30/30 ?
4) INSTALL AUTO SHUT OFF AT CONDENSATE 2ND LINE C/O IN FRONT OF TRAP
5) C/O CAP COVER EAST WALL
6) WHAT IS 3/4" DIAMETER PIPE NIPPLE CAP ? EAST EXT.
7) LOOSE RECEPT IN LAUNDRY
8) BRING FLOOR CHASE FOR GAS ABOVE CABINET AND SEAL
9) NEED GAS VALVE AND CAP AT PATIO; FINISH FLOOR DRAINS AT PATIO
10) INSTALL 90 DEGREE ELBOWS ON T & P'S AND CONDENSATE
11) T & P VALVE AT SOLAR ? HTR
12) HOUSE ADDRESS