Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM03836
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
07/16/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BROKEN INSULATION ON ALL FEEDER SERV. TAPE 2) REDUCE BREAKERS ON A/C TO WIRE DIAMETER A/C LABEL EXAMPLE 50/50 #8 AC 30 AMP CIRCUIT 3) MARK FUSE SIZE GARAGE UNITS 30/30 ? 4) INSTALL AUTO SHUT OFF AT CONDENSATE 2ND LINE C/O IN FRONT OF TRAP 5) C/O CAP COVER EAST WALL 6) WHAT IS 3/4" DIAMETER PIPE NIPPLE CAP ? EAST EXT. 7) LOOSE RECEPT IN LAUNDRY 8) BRING FLOOR CHASE FOR GAS ABOVE CABINET AND SEAL 9) NEED GAS VALVE AND CAP AT PATIO; FINISH FLOOR DRAINS AT PATIO 10) INSTALL 90 DEGREE ELBOWS ON T & P'S AND CONDENSATE 11) T & P VALVE AT SOLAR ? HTR 12) HOUSE ADDRESS |