Permit: T06CM03836

Parcel: 141015530

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM03836

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/10/2007 FRAMING Approved IVRS - Inspection :*
08/07/2007 FRAMING Partial Approval IVRS - Inspection :*
1) NEED SHEAR TRANSFER DETAIL AT INTERIOR SHEARWALL
07/31/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BLOCK MECH IN DINING
2) SECURE H20 LINE SOFT H20 LOOP
3) 1/2" DIAMETER A.B. AT ALL SHEARWALLS, USE ENGINEER DETAIL FOR BLKS AT TOP OF WALL
4) BLK AT DIRECT VENT
5) NEED INSULATOR AT H20 LEFT OF FIREPLACE
6) ROMEX INSULATOR ABOVE S/WEST DOOR
7) NEED GOOD SEAL ON GAS LINE CHASE
8) TWO MANY WIRES IN BOXES AT FRONT DOOR
9) NEED DETAIL FOR PERPENDICULAR RAFTER TO SHEAR WALL TRANSFER
10) STRAP GAS LINE AT GARAGE
11) H.D.'S NEED INFORMATION DIFFERENT H.D.'S USED, CAN THEY BE USED ON A SINGLE STUD ?
07/20/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ISOLATE CU. LINE SET TO METAL STUDS
2) ISLAND GAS UNCOVER SLEEVED SECTION (PRESSURE TEST) OK
3) BLK ALL MECH DUCTS
4) H.D.'S WHAT IS A STIF CLIP CL60 ?, ATTACHED TO DBL STUD ?
5) INTERIOR GYP. SHEARWALLS NOT A.B. TO FLOOR, NO SHEAR TRANSFER DETAILS
6) SW4 OSB INTERIOR SHEAR
7) I DON'T UNDERSTAND H20 SYSTEM W/HTR #1
8) GARAGE TO HOUSE SW3, NO A.B.'S, NO SHEAR TRANSFER
9) BLOCK UNDER SCUPPER AREAS
10) COMBUSTION RELIEF DUCTS
11) ROMEX, COMM. WIRE NEED INSULATORS AT STEEL, CEILING CHECK THRU OUT
12) ROMEX HANGING FROM KIT CEILING ? 1/2 WAY THRU KIT FROM GARAGE
13) STOPPED INSPECTION
07/18/2007 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) WALL PLATE CHANNELS REQUIRE METAL STUD REINFORCING PER FIGURE R603.3.1 (1)
2) ANCHOR BOLTS REQUIRED WITHIN 12" OF PLATE ENDS
3) TRACK SPLICES NOT PER IRC R603.3.6
4) BUILT UP STUD POSTS NOT SCREWED TOGETHER AT 24" ON CENTER
5) #1 SHEARWALLS REQUIRE ANCHOR BOLTS AT 48" ON CENTER
6) DETAIL 29 AND 30 NOT COMPLIED WITH
7) STOPPED INSPECTION-TOO MANY ITEMS
8) HOUSE NOT BUILT PER PLAN/CODE