Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM03833
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/18/2010 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
03/13/2010 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL MAX 30/30 FUSES FURN. 2) INSTALL BUSHING AT FURNACE STAT WIRE WHERE ENTERS CABINET OF FURN. |
|
02/28/2010 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) FURNACE (ATTIC TYPE) LABEL UNIT FOR AMPS CIRCUIT SIZE 2) FURNACE HAS BEEN VADALIZED COVER REMOVED, CHECK INSIDE AND MAKE ROOM FOR FALSE COVER REMOVAL 3) NEED STUCCO CERT AND INSULATION CERT |
|
11/06/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) SECURE A/C CONDENSOR FLEX CONDUIT WITHIN 12" OF DISCONNECT 2) PROVIDE POST TENSION TAG AT WATER SHUT OFF VALVE 3) REPAIR DAMAGED WIRE AND LABEL IRRIGATION CIRCUIT 4) IMPROPER COLOR CODE OF A/C WIRES WHITE CANNOT BE HOT 5) NO REAR PORCH LIGHT OR BALCONY LIGHT 6) BALCONY DRAIN CANNOT HAVE OPENING GREATER THAN 4" 7) PROVIDE 1/4" PER FOOT PITCH ON A/C DRAIN PAN 8) SECURE FURNACE WHIP WITHIN 12" OF DISCONNECT 9) WIRE COLOR CODE WRONG 10) SECURE WIRE WITHIN 8" OF DISCONNECT 11) MARK FAU HEAT STRIP LABEL 12) STOPPED INSPECTION-TO MANY ITEMS 13) NO PLAN ON SITE |