Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM03833
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2007 | FRAMING | Approved | IVRS - Inspection :* | |
02/07/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PENDING TRUSS REPAIRS |
|
11/30/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LATHE NOT COMPLETE FRONT OVER PATIO 2) SEAL ALL LATHE PENETRATIONS 3) FLOOR TRUSS IN GARAGE TOP CHORD CUT BY PLUMBING. PROVIDE CITY OF TUCSON APPROVED TRUSS REPAIR DOCUMENT 4) PLAN CALLS FOR FLOR TRUSSES AT 16" ON CENTER INSTALLED AT 24" ON CENTER. BUILD TO PLAN OR REVERSE PLAN TO AS BUILT 5) 4 X 12 BEAM CARRING FLOOR TRUSSES IS NOT ON PLAN. REVISE PLAN. WHAT IS IT TO BEAR ON ? 6) STAIR HEADER TRUSS CUT. PROVIDE CITY OF TUCSON APPROVED ENGINGEERING REPAIR 7) PROVIDE APPROVED TRUSS DRAWINGS 8) STAIRS EXCEED 7 3/4" RISE 9) STOPPED INSPECTION-TOO MANY ITEMS |
|
11/27/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE LATHE 2) COMPLETE 2ND FLOOR PATIO OVER GARAGE 3) TIGHTEN ANCHOR BOLTS 4) CONNECT POWDER ROOM EXHAUST FAN 5) COMPLETE FHA STRAP NAILING 6) CLEANOUT HOUSE FOR INSPECTION 7) STOPPED INSPECTION |
|
11/22/2006 | FRAMING | Cancelled | CANCELLED PER CEASAR OF SIERRA PACIFIC HOMES #349-6289 |