Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2008 | FIRE - FINAL | Approved | Approved, 3/7/08. | |
| 03/06/2008 | FIRE - FINAL | Denied | 1.) Lable door for electrical room. 2,) Provide EXIT sign in kitchen area. 3.) Remove keyed-lock from exterior door in the laundry room area. Replace with thumb-turn lock or panic hardware. 4.) Tables stored in closet room in meeting room area are obstructing the sprinkler head. 5.) Inspect sprinkler heads through out building. Multiple sprinkler covered with plaster or paint. Shall clean or replace. 6.) Lable door for equipment room, "EQUIPMENT ROOM". 7.) Opening in wall in the ADMIN. room. 8.) Ballast light to close to sprinkler deflector. 2nd. floor, south room storage room. 9.) Ballast light to close to spklr. defector. 3rd. floor, closet. 10.) Lable Riser room. |
|
| 03/04/2008 | FIRE - FINAL | Partial Approval | OK TCO PER CONVERSATION WITH LARRY LAKEY. FIRE INSPECTOR WILL NEED TO CONFIM STATUS OF SPRINKLER PERMIT T07BU02003 AS EITHER FINAL OR WITHDRAWN. TWO OTHER PERMITS FOR SPRINKLERS HAVE BEEN APPROVED. |