Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2008 | MECHANICAL - ABOVE CEILING | Approved | ||
| 01/23/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* RESTROOMS OK |
|
| 01/16/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR CORR. N. OF ELEVATOR & ELEV. LOBBY OK TO ROCK |
|
| 01/15/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* NO ONE AVAILABLE ON SITE |
|
| 01/14/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* VENT PIPING TOO CLOSE (TOUCHING) COMBUSTIBLE |
|
| 01/10/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* PUBLIC RESTROOMS 1ST FLOOR |
|
| 12/31/2007 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1ST FLOOR BREAKROOM - INSULATE"Y" FITTING PROVIDE STRAPS AS NEEDED - CORRIDOR FIRE DAMPERS NEED SEALER - OPEN TAP IN DUCT WORK |
|
| 12/11/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PUBLIC AREA MECHANICAL OK TO ROCK |
|
| 11/15/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PRE-FUNCTION PROVIDE LETTER FROM ENGINEER ON DAMPER LOCATION MEETING ROOMS OK TO ROCK THIRD FLOOR OK ROCK |
|
| 11/08/2007 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/28/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - DISCUSSED TYPE 1 HOOD CLEARANCES FROM WOOD WALLS - HAVE ARCHITECT REDESIGN WALL - INSTALL DIRECT VENT APPLIANCES PER MANUFACTURES INSTRUCTIONS |