Permit: T06CM03798

Parcel: 140410530

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
04/02/2008 MECHANICAL - ABOVE CEILING Approved
01/23/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
RESTROOMS OK
01/16/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1ST FLOOR CORR. N. OF ELEVATOR & ELEV. LOBBY
OK TO ROCK
01/15/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
NO ONE AVAILABLE ON SITE
01/14/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
VENT PIPING TOO CLOSE (TOUCHING) COMBUSTIBLE
01/10/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
PUBLIC RESTROOMS 1ST FLOOR
12/31/2007 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1ST FLOOR
BREAKROOM - INSULATE"Y" FITTING PROVIDE STRAPS AS NEEDED

- CORRIDOR FIRE DAMPERS NEED SEALER
- OPEN TAP IN DUCT WORK
12/11/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PUBLIC AREA MECHANICAL OK TO ROCK
11/15/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PRE-FUNCTION PROVIDE LETTER FROM ENGINEER ON DAMPER LOCATION
MEETING ROOMS OK TO ROCK
THIRD FLOOR OK ROCK
11/08/2007 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/28/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- DISCUSSED TYPE 1 HOOD CLEARANCES FROM WOOD WALLS
- HAVE ARCHITECT REDESIGN WALL
- INSTALL DIRECT VENT APPLIANCES PER MANUFACTURES INSTRUCTIONS