Permit: T06CM03798

Parcel: 140410530

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/10/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
04/09/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/03/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
TIKI BAR OK
03/31/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE CERTS FOR BACKFLOW
2. PROVIDE SUPPORT ON ALL DRAIN PIPING
3. PAINT VENT THRU ROOF
03/06/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. COMPLETE LIST FROM 3/4/08 3 THRU 5
2. PROVIDE FULL SIZE CLEANOUT FROM TIKI BAR
03/04/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. MAKE OUTSIDE CLEAN WATER & GAS TIGHT
2. RAISE FLOOR DRAIN IN MENS RESTROOM LOBBY
3. PROVIDE APPROVED PLANS FOR GAS GROUND FLOOR UNITS
4. COMPLETE TIKI BAR
5. COMPLETE ROOF DRAINS ON ALL SIDES OF BUILDING
02/25/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE APPROVED DRAIN FOR DISHWASHER
2. PROVIDE DRAINAGE FITTING FOR PRE-UP SINK
3. PROVIDE DRAIN 009 BACKFLOW AND CERTS
4. PROVIDE APPROVED SUPPORT FOR SODA DRAINS

1. 1ST FLOOR HALL RESTROOM SUPPORT MIXING VALVE
2. PROVIDE 1" AIR GAP FOR WATER HEATER T&P
3. PROVIDE MEANS FOR WATER HAMMERING ICE MAKER AND DAP SINK IN BREAKROOM
4. PROVIDE WATER SUPPLY FOR SOAP ARSENAL II AT MOP SINK WITH BACKFLOW PROTECTION
5. PROVIDE MEANS FOR WATER HAMMERING IN GUEST LAUNDRY & HALL LAUNDRY

1. PROVIDE MEANS FOR WATER HAMMERING AT ALL WASHERS
2. COMPLETE ALL GAS PIPING AND COMPLETE LIST
FROM 2/21/08
3. LIST MAY NOT BE COMPLETE
4. COMPLETE TIKI BAR

1. COMPLETE LOBBY RESTROOMS
2. LIST MAY NOT BE COMPLETE
3. PROVIDE APPROVED GAS DRAWINGS
02/19/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. 3RD & 2ND FLOOR ROOMS OK ONLY
2. GAS PRESSURE TEST INSIDE HOTEL FOR GAS PIPING OK
02/11/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*