Permit: T06CM03798

Parcel: 140410530

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/14/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/12/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
COMPLETE WORK BEFORE CALLING FOR INSPECTION
02/15/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/15/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET FLANGE IN LOBBY RESTROOM OK
01/11/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ADA SHOWERS TEST OK
2. CLOSET FLANGES ON ALL ROOMS OK
3. PER REDLINE DRAWING FOR ROOF DRAINS
FOR OVERHEAD OK AND LETTER FROM ENGINEER
01/10/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ADA SHOWERS 1ST & 2ND FLOORS OK
THIRD FLOOR #229 OK
01/09/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. GAS PIPING TO TIKI BAR PER REDLINE DRAWING ON P502 TEST OK - REDLINES TO BE APPROVED BY CITY OF TUCSON
2. YARDWATER TO TIKI BAR TEST OK
3. PROVIDE TEST ON ADA SHOWERS
01/07/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROVIDE COMPLETE TEST ON SHOWERS
2. PROVIDE APPROVED DRAWING ON POOL HOUSE
01/03/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. TEST ON 1" GAS TO POOL HOUSE TEST OK
2. 1" PEX WATER TO POOL HOUSE TEST OK
12/11/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND FLOOR CLOSET FLANGE OK
12/10/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD FLOOR AND SOUTH SIDE OF 2ND FLOOR CLOSET FLANGES OK
12/07/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD FLOOR FROM SOUTHSIDE TO ROOM #332
12/04/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CALL BACK FOR YARDWATER
11/19/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) INSTALL GAS PIPING PER APPROVED PLANS
11/15/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE APPROVED FOR CHANGES FROM COPPER MAIN IN BOILER TO CPVC
11/13/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PIPING AND VENT PIPING FOR ? INTERCEPTOR OK
2) SPA TUB TEST OK
3) TWO NORTH LOBBY ROOF DRAINS OK
11/07/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE APPROVED PLANS FOR ROOF DRAIN CHANGES
2. 1ST FLOOR LAUNDRY ROOM WATER PIPING IN WALL
TEST OK
11/02/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. GAS PIPING IN WALL FOR FINISH KITCHEN ONLY OK TEST
2. UNCOVER WALL WITH PLUMBING TO BE INSPECTED IN WALLS
10/26/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PUBLIC RESTROOM TEST OK IN WALLS
2. KITCHEN AREA OK IN WALLS
10/25/2007 PLUMBING - INTERMEDIATE Not ready for Inspection COMPLETE WORK FROM LAST INSPECTION
10/23/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROVIDE APPROVED DRAIN FOR DISPOSER
2. PROVIDE APPROVED DRAINS FOR SINK
3. COMPLETE WORK IN RESTROOM
10/05/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
LAUNDRY AREA DWV WATER TEST THRU ROOF OK
UNITS 212, 214 SHOWER WATER TEST OK
1 1/2 HOUR FROM 3RD TO 1ST LEVEL WATER TEST OK
10/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND LEVEL FROM ELEVATOR SOUTH TUBS & SHOWER WATER TEST ALL EXCEPT UNITS #212 & 214

1. SHALL PROVIDE CORRECT DRAINAGE FOR FLOOR SINKS & FLOOR DRAINS 2ND LEVEL ICE MACHINE FROM 1ST LEVEL 2ND LEVEL ROOMS 204-211, 215-221, WATER TEST THRU LEVEL 3 SAME ROOMS THRU ROOF WATER TEST OK SUPPORT THIS PIPING CORRECTLY LEVEL 1 CEILING SPACE
09/26/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
TUB & SHOWER WATER TEST ELEVATOR SHAFT
3RD LEVEL SOUTH ROOM UNITS OK
WASTE & VENT WATER TEST
ROOM #126, FLOOR SINK SPRINKLER RISER ROOM,
MECH ROOM 142 OK
ROOM #147 WATER TEST DWV OK
09/24/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNITS 2ND & 3RD LEVEL FROM ELEVATOR SOUTH #202-224 #304 - 324 WATER TEST THRU ROOF AND WATER DISTRIBUTION IN UNITS ONLY OK
09/21/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. REPAIR LEAKS ON ALL PIPING
2. ADD SUPPORT ON ALL PIPING
09/17/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. REPAIR LEAK AT ROOM #147, OTHER ROOMS FOR 1ST & 3RD FLOOR TEST
OK TO ELEVATOR LOBBY, PROVIDE TEST ON HANDICAP SHOWER ON ALL FLOORS TO BE TESTED AT LATER DATE.
09/14/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND FLOOR TUBS FROM NORTH TO ELEVATOR LOBBY
09/10/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. GAS PIPING TEST FROM STUB INTO 1ST FLOOR HALL
AND STUB THRU ROOF FOR PRV #5 AND #7 OK
2. ROOF DRAINS AND OVERFLOW, RTU#92 TEST OK
09/06/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER WASTE & VENT AND WATER FROM NORTHSIDE OF BUILDING TO ELEVATORS LOBBY #200 PER ENGINEER APPROVAL.
09/04/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER PIPING IN ROOMS ONLY FROM NORTH SIDE OF BUILDING TO ELEVATOR LOBBY #200
08/30/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. 2ND & 3RD FLOORS WASTE FROM NORTHSIDE TO #353, #327
#253, #227 PER ENGINEER APPROVAL, TEST OK, PROVIDE TEST ON FIRST FLOOR
2. PEX APPROVED BY GERALD M REMBOUSKI IN
LIEU OF TYPE L COPPER
08/13/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. INSTALL WATER PIPING MATERIAL PER APPROVED PLANS
2. SOLVENT PIPING INSTALL PER APPROVED PLANS
06/19/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
READ LIST FROM 6/14/07 INSTALL PER APPROVED PLANS
06/14/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SHALL ? TEST ON ALL PIPING, SHALL INSTALL PER APPROVED PLAN OR HAVE REVISED CITY APPROVED PLAN ON SITE, CORRECT DRAINAGE AND VENT FITTINGS SHALL BE USED. ALL PIPING TO BE CORRECTLY SUPPORTED
05/21/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
TEST FROM UNDERGROUND PIPING TO FIRST AERATOR ON FIRST FLOOR OK