Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/27/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SEAL CAMERA CABLES PER 501.15(D) *RECEIVED LETTER FOR 514.13 & DERATING |
|
| 02/26/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SEPARATE TO SEAL CONDUCTORS IN MULTI-CABLES 2. CENTER CONDUCTORS IN PACKING FOR SEALS 3. PLEASE PROVIDE A LETTER FOR VERIFICATION OF 514.23 4. DERATE CONDUCTORS PER 310.15 (12 CONDUCTORS) 5. TIGHTEN LOOSE FITTINGS - CANOPY 6. SUPPORT 2 1/2" SEALTITE WITHIN 4' OF FITTINGS AND EVERY 10' 7. SECURE VDV CABLING TO BOX & CABLES TO BE FOR WET LOCATION OK TO POUR SEALS AFTER CORRECTIONS ARE MADE |
|
| 02/25/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |