Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/31/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DOUBLE WALL VENT TO EXTEND 2' ABOVE EVAP. COOLER WITH AN APPROVED CAP & FLASHING |
|
| 06/30/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REMOVE UPSIDE DOWN PIECE OF DOUBLE WALL PIPE FROM VENT CONNECTOR. DOUBLE WALL VENT ABOVE CEILING ALSO UPSIDE DOWN. GAS FLEX CANNOT PENETRATE CABINET OF FURNACE & CANNOT EXCEED 3' IN LENGTH. SEE LISTING FOR PROPER SIZING. YOU MUST USE A LICENSED CONTRACTOR ON RENTAL PROPERTIES. PLEASE SHOW VERIFICATION. LEAVE CEILING OPEN IN CLOSET TO INSPECT VENT REPAIR. PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR. DO NOT USE TAPE. |